ELPA 3
Description
- Staircase time switch, electronical
- Additional multi-voltage input electrically isolated for AC/DC 8...240 V, e.g. f眉r intercoms
- Immediate secondary switching
- Toggle switch for permanent light
- Terminal layout same as ELPA 8
- Extremely accurate
- Push button input with electronic overload protection
- Automatic 3 or 4 conductor detection (4 conductor with connection for floor lighting, 3 conductor no longer permitted for new systems)
Technical data
Operating voltage | 220聽鈥撀240 V AC |
Frequency | 50聽鈥撀60 Hz |
Width | 1 modules |
Installation type | DIN rail |
Stand-by consumption | ~0,7 W |
Capacity loss max. | 1,2 W |
Glow lamp load | 150 mA |
Setting range time | 0,5聽鈥撀20 min |
Type of connection | 3-/4-conductors |
3/4-way conductors | Automatic |
Secondary switching | At once |
Duty cycle in per cent | 100 |
Type of contact | NO contact |
Opening width | < 3 mm (碌) |
Switching output | Not potential-free (230 V) |
Incandescent/halogen lamp load | 2300 W |
Fluorescent lamp load (conventional) lead-lag circuit | 2300 VA |
Fluorescent lamp load (conventional) parallel-corrected | 400 VA 42 碌F |
Energy saving lamps | 90 W |
LED lamp | < 2 W = 20 W or 2-8 W = 55 W or > 8 W = 70 W |
Fluorescent lamp load (electronic ballast) | 350 W |
Fluorescent lamp load (conventional) series-corrected | 2300 VA |
Fluorescent lamp load (conventional) not corrected | 2300 VA |
Switching capacity |
10 AX (at 230 V AC, cos 蠁 = 0.3), 16 A (at 230 V AC, cos 蠁 = 1) |
Switch for permanent light | Sliding switch |
Test approval | VDE |
Housing and insulation material | High-temperature resistant, self-extinguishing thermoplastic |
Ambient temperature | -25 掳C聽鈥β+50 掳C |
Protection class | II |
Type of protection | IP 20 |