ELPA 9
Description
- Staircase time switch, electro-mechcanical
- 3 conductor connection and floor lighting, but without secondary switching (no longer permitted for new systems)
- Terminal layout same as ELPA 8
- No closed-circuit current consumption
- Toggle switch for permanent light ON
- Reliable due to synchronous motor drive
- Simplest possible time setting and direct delay time readout on absolute scale
- Precision mechanics and therefore exact switching period
- Very low sensitivity to interference
Technical data
| Operating voltage | 230 V AC |
| Frequency | 50 Hz |
| Width | 1 modules |
| Installation type | DIN rail |
| Stand-by consumption | ~0 W |
| Glow lamp load | 50 mA |
| Setting range time | 1聽鈥撀7 min |
| Type of connection | 3-way conductor |
| 3/4-way conductors | Only 3-way conductor |
| Secondary switching | No |
| Type of contact | NO contact |
| Opening width | > 3 mm |
| Switching output | Not potential-free (230 V) |
| Incandescent/halogen lamp load | 2300 W |
| Fluorescent lamp load (conventional) lead-lag circuit | 2300 VA |
| Fluorescent lamp load (conventional) parallel-corrected | 1300 VA 70 碌F |
| Energy saving lamps | 150 W |
| LED lamp | < 2 W = 30 W or 2-8 W = 90 W or > 8 W = 100 W |
| Fluorescent lamp load (electronic ballast) | 600 W |
| Fluorescent lamp load (conventional) series-corrected | 2300 VA |
| Switching capacity |
6 AX (at 230 V AC, cos 蠁 = 0.3), 16 A (at 230 V AC, cos 蠁 = 1) |
| Switch for permanent light | Toggle switch |
| Housing and insulation material | High-temperature resistant, self-extinguishing thermoplastic |
| Ambient temperature | -10 掳C聽鈥β+50 掳C |
| Protection class | II |
| Type of protection | IP 20 |