LUNA 110 AL 24V
Description
- Analogue twilight switch
 - External light sensor included in delivery
 - Adjustable On and Off switching delay
 - to avoid faulty operation caused by lightning, car headlights etc.
 - Display of channel and switching status
 - DuoFix spring terminals
 - for 2 conductors per connection terminal
 - Extended brightness levels and adjustable delay
 - Five adjustable brightness levels for simple setting of lux value
 - Zero-cross switching for relay-saving switching and high lamp loads (not with 24 V devices)
 - Permanent OFF and permanent ON function can be set on the potentiometer
 - Test function
 - for monitoring installation independent of set brightness value
 - Infinitely adjustable switching brightness
 
Technical data
| Operating voltage | 12聽鈥撀24 V UC | 
| Frequency | 50聽鈥撀60 Hz | 
| Number of channels | 1 | 
| Stand-by consumption | ~0,2 W | 
| Setting range brightness | 2聽鈥撀50000 lx | 
| Switch-on delay | 0聽鈥撀20 min | 
| Switch-off delay | 0聽鈥撀20 min | 
| Type of contact | Changeover contact | 
| Switching output | Potential-free | 
| Width | 2 modules | 
| Installation type | DIN rail | 
| Type of connection | DuoFix spring terminals | 
| Keyboards | 3 potentiometers | 
| Switching capacity | 
                   16 A (at 250 V AC, cos 蠁 = 1), 2 AX (Fluorescent lamp load)  | 
            
| Switching capacity min. | <10 mA | 
| Incandescent lamp load | 1400 W | 
| Halogen lamp load | 1400 W | 
| Fluorescent lamp load (conventional) parallel-corrected | 58 W 7 碌F | 
| Energy saving lamps | 5 x 7 W, 4 x 11 W, 4 x 15 W, 4 x 20 W, 4 x 23 W | 
| Fluorescent lamp load (electronic ballast) | 180 W | 
| Housing and insulation material | High-temperature resistant, self-extinguishing thermoplastic | 
| Ambient temperature | -30 掳C聽鈥β+55 掳C | 
| Type of protection | IP 20, sensor IP 55 | 
| Protection class | II, Sensor III | 
| Max. cable length to sensor | 100 m | 

               
               